SPECIFICATIONS:
Calconduit RIGID conduit is manufactured in accordance with the latest edition of the following:
● American National Standard for Rigid Steel Tubing (ANSI® C80.1)
● Underwriters Laboratories Standard for Rigid Steel Tubing (UL6)

File No. E226472
|
| Trade Size |
Nominal Wt. per 100 Ft. - With couplings |
Nominal Outside Diameter |
Nominal Wall Thickness |
Length With Coupling |
Bundle Quantities |
| Inches |
Pounds |
Inches |
Inches |
Feet |
Pieces |
Feet |
Pounds |
| ½ |
82 |
0.840 |
0.104 |
10 |
127 |
1,270 |
1,042 |
| ¾ |
109 |
1.050 |
0.107 |
10 |
91 |
910 |
992 |
| 1 |
161 |
1.315 |
0.126 |
10 |
91 |
910 |
1,465 |
| 1¼ |
218 |
1.660 |
0.133 |
10 |
61 |
610 |
1,330 |
| 1½ |
263 |
1.900 |
0.138 |
10 |
61 |
610 |
1,604 |
| 2 |
350 |
2.375 |
0.146 |
10 |
37 |
370 |
1,295 |
| 2½ |
559 |
2.875 |
0.193 |
10 |
19 |
190 |
1,062 |
| 3 |
751 |
3.500 |
0.205 |
10 |
19 |
190 |
1,427 |
| 3½ |
880 |
4.000 |
0.215 |
10 |
19 |
190 |
1,672 |
| 4 |
1030 |
4.500 |
0.225 |
10 |
19 |
190 |
1,957 |
| 5 |
1400 |
5.563 |
0.245 |
10 |
7 |
70 |
980 |
| 6 |
1840 |
6.625 |
0.266 |
10 |
7 |
70 |
1,288 |
Applicable tolerances: Length: 10Ft ± ¼”
Outside Diameter: ½”-2” ±0.015” ; 2½”-4” ±0.025” ; 5”-6” ± 1% |